✔ Communication Protocol

What is Modbus RTU over TCP? One way to use serial Modbus devices over a network

Modbus RTU over TCP (Modbus over TCP) sends the Modbus RTU message unchanged, exactly as it is, inside a TCP connection.

Despite the similar name, it is not the same as standard Modbus TCP. It usually appears in the "transparent" mode of serial-to-Ethernet converters. You need to know which mode the other side uses; otherwise there will be no communication.

Highlights

  • Serial-to-Ethernet converter
  • Transparent mode
  • RTU frame + CRC
  • Bringing old devices onto the network

How is it different from Modbus TCP?

Modbus TCPModbus RTU over TCP
Message formatModbus TCP header (MBAP), no CRCRTU message as is, including CRC
What the converter doesTranslates to RTU (gateway mode)Does not touch it, just carries it (transparent mode)
Several clients at onceYes, the gateway queues themUsually no
CompatibilityWorks with all Modbus TCP softwareSoftware must support this mode

The most common mistake: the converter is in transparent mode but standard Modbus TCP is selected in the software (or vice versa). The device seems to connect, but no data arrives.

When is it used?

  • When older devices on a serial line need to be read over the network without rewiring
  • When an RS-485 line at a remote site must be carried to the centre over 4G or the internet
  • When existing software expects a network connection that behaves like a serial port

Hardware architecture

SCADARTU over TCP clientNetwork / 4G / VPNno distance limitSerial-to-Ethernet Convertertransparent modeRS-485 Line~1200 m limitModbus RTU Devicesanalyser, meter
  • Serial-to-Ethernet converter (device server): RS-485 (or RS-232) on one side, Ethernet on the other. Choose industrial, DIN-rail, isolated models.
  • Remote site: The converter can be connected to a 4G router to bring the site to the centre.
  • Serial side: The line behind the converter is still an RS-485 line; all RS-485 rules (cable, termination, 1200 m) apply.

Cable and material selection

  • Serial side: 120 Ω shielded twisted-pair RS-485 cable with termination resistors at the line ends.
  • Network side: Cat6 (shielded in noisy areas), fibre over long distances, an industrial 4G router at remote sites.
  • Converter settings: Serial settings (speed, parity, stop bits) must match the devices; choose the operating mode (TCP server/transparent or Modbus gateway) deliberately.
  • Timeouts: 4G and internet links add latency, so set longer timeouts in the software than on a serial line.

What about distance?

There are two distances in this setup. On the network side (between the centre and the converter), Ethernet, fibre or the internet is used, so there is no practical limit. On the serial side (between the converter and the devices), RS-485's limit of about 1200 metres still applies. So the distance between centre and site is solved, but the devices must stay close to the converter.

Advantages and disadvantages

Advantages

  • Older serial devices are brought onto the network without being replaced
  • Removes the distance limit between centre and site
  • No protocol translation in the converter, so setup is simple
  • A low-cost transition solution

Disadvantages

  • Not standard Modbus TCP; not every software supports it
  • The serial line's speed and distance limits remain
  • Usually only one client can connect at a time
  • Latency on remote links requires timeout tuning
  • No security; use a VPN

Which one should I choose?

SituationRecommendation
Your software supports standard Modbus TCPPut the converter in Modbus gateway mode and use Modbus TCP
Several systems will read the same devicesModbus gateway mode (Modbus TCP)
The software only works with serial-port logicRTU over TCP or a virtual COM port
Devices are being purchased newChoose devices with built-in Modbus TCP

How to test it

  1. Open the converter's web interface and note its operating mode and TCP port.
  2. Check that the serial settings match the devices on the line.
  3. In the test software, choose the connection type that matches the converter's mode (RTU over TCP or Modbus TCP).
  4. Read a known register; if you get timeouts, increase the timeout.

Testing with ATLAS SCADA

If you put the converter in Modbus gateway mode, you can test the line with ATLAS SCADA as a standard Modbus TCP connection and see the serial devices' values directly on the SCADA screen.